Am I subject to the logbook obligation?

Whether a refrigeration installation is subject to the leak-check and logbook obligation depends on the CO₂ equivalent: refrigerant charge × GWP. Choose your refrigerant and charge below — you will see immediately where you stand.

BRL 100 and STEK are Dutch national certification schemes — full support today is NL-only. See our honest country-coverage disclosure.

GWP = global warming potential (CO₂ = 1), per EU 2024/573 Annex I.

kg

The total refrigerant content of the installation. Slide or type your own value — above 50 kg you can type the number directly.

Calculation: 3 kg × GWP 2088

CO₂ equivalent

6.26 tonnes CO₂-eq

Subject to the logbook obligation
Annual leak check (≥ 5 tonnes)

This installation must keep a logbook with all refrigerant changes and leak checks, and is required to be checked for leakage periodically.

Indicative. Calculated as charge × GWP (AR4) per Annex I of EU 2024/573. For hermetically sealed systems the threshold is higher (from 10 tonnes CO₂ equivalent). An approved leak detection system can halve the required check frequency. Always consult your certification body for your specific situation.

The thresholds at a glance

≥ 5 tonnes CO₂-eq

Annual leak check

Logbook mandatory. Check for leakage at least once a year.

≥ 50 tonnes CO₂-eq

Six-monthly leak check

Twice a year. A logbook with all changes remains mandatory.

≥ 500 tonnes CO₂-eq

Fixed detection system

Leak detection system mandatory, in addition to the six-monthly check.

Hermetically sealed systems: the first threshold is at 10 tonnes CO₂ equivalent.

Frequently asked questions

When is a refrigeration installation subject to the logbook obligation?

An installation with 5 tonnes CO₂ equivalent or more is subject to the logbook and leak-check obligation. The CO₂ equivalent is the refrigerant charge (kg) multiplied by the GWP of the refrigerant. Hermetically sealed systems have a higher limit of 10 tonnes.

How often do I need to carry out a leak check?

From 5 tonnes CO₂ equivalent annually, from 50 tonnes every six months, and from 500 tonnes a fixed leak detection system is mandatory in addition to the six-monthly check. An approved leak detection system can halve the required frequency.

What is CO₂ equivalent?

The amount of refrigerant (kg) multiplied by the GWP (global warming potential) of that refrigerant. Example: 3 kg of R410A (GWP 2,088) is 6,264 kg, or just over 6 tonnes CO₂ equivalent.

Does the logbook obligation also apply to air conditioners and heat pumps?

Yes. The threshold depends on the CO₂ equivalent, not on the type of installation. An air conditioner or heat pump with a sufficiently high-GWP refrigerant falls under it just as much as a refrigeration installation.

What needs to be in the logbook?

Among other things, the refrigerant changes (top-up, draining, recovery), the leak checks carried out with date and result, and who carried out the work.