Glossary

The terms from refrigeration engineering, F-gas regulations and certification — explained in plain language. Click through for more depth, or calculate directly whether an installation is subject to the logbook obligation.

BRL 100 and STEK are Dutch national certification schemes — full support today is NL-only. See our honest country-coverage disclosure.

Regulations & obligations

The European F-gas rules and what they concretely require from a refrigeration company.

F-gases

Fluorinated greenhouse gases: synthetic gases widely used as refrigerant that have a strong greenhouse effect.

F-gases trap heat many times more strongly than CO₂. That is why the EU regulates their use strictly: leak checks, certification, registration and a gradual phase-down of the most harmful types.

See also: HFC, GWP, EU 517/2014, EU 2024/573

EU 2024/573

The revised F-gas Regulation (in force since 11 March 2024) that replaces 517/2014 and accelerates the phase-down of HFCs.

The Regulation tightens the phase-down, sets extra requirements for equipment with high-GWP refrigerants and steers towards an almost complete HFC phase-out. For most installation companies the practical duties — leak checks, logbook, certified staff — stay the same, but the choice of refrigerant shifts.

See also: EU 517/2014, F-gas phase-down, F-gas quota

Logbook obligation

The obligation to keep a logbook per installation with ≥5 tonnes CO₂ equivalent, recording refrigerant changes and leak checks.

The threshold is determined by refrigerant charge (kg) × GWP. Hermetically sealed systems have a higher limit (from 10 tonnes CO₂ equivalent). Not sure whether an installation falls under it? Calculate it below.

See also: CO₂ equivalent, Leak check, Installation logbook

Leak check

Periodic check for refrigerant leakage; the frequency depends on the CO₂ equivalent of the installation.

Guideline: from 5 tonnes CO₂ equivalent annually, from 50 tonnes every six months, and from 500 tonnes a fixed leak detection system is mandatory (in addition to the six-monthly check). A correct leak detection system can halve the required frequency.

See also: Leak detection system, CO₂ equivalent, Logbook obligation

Leak detection system

A permanently installed system that automatically detects refrigerant leakage; mandatory from 500 tonnes CO₂ equivalent.

See also: Leak check, CO₂ equivalent

Certification & accreditations

BRL 100, BRL 200, STEK and BRL K25000 — who is allowed to work on refrigerant or gas combustion installations.

BRL K25000

Kiwa's certification scheme for CO safety certification of gas combustion installations under the Dutch statutory CO certification scheme (Bbl) — an alternative route, assessed partly remotely, aimed at sole traders and small companies alongside BRL 6000-25.

BRL K25000 is about carbon monoxide prevention in gas combustion installations, not about refrigerants or F-gases. In the refrigeration sector the term is sometimes used incorrectly for the annual BRL 100 surveillance audit — that is a different, unrelated check on refrigerant administration.

See also: Certification body (CI)

Raad voor Accreditatie (RvA)

The Dutch organisation that accredits certification bodies and so safeguards the reliability of certificates.

See also: Certification body (CI)

Refrigerants & GWP

Commonly used refrigerants, their global warming potential and the CO₂-equivalent calculation.

GWP

Global Warming Potential: how much more strongly a gas warms than CO₂ over 100 years. CO₂ has a GWP of 1.

The higher the GWP, the faster an installation reaches the logbook and leak-check thresholds. R290 (propane) has a GWP of 3; R404A has a GWP of 3,922 — more than a thousand times higher.

See also: CO₂ equivalent, HFC, Natural refrigerant

HFC

Hydrofluorocarbons: the most widely used synthetic F-gas refrigerants (such as R410A and R134a), often with a high GWP.

See also: F-gases, HFO, GWP

HFO

Hydrofluoroolefins: newer refrigerants with very low GWP, such as R1234yf, that are replacing high-GWP HFCs.

See also: HFC, GWP, R1234yf

R134a

HFC with a GWP of 1,430; used among other things in refrigeration and older car air conditioning.

See also: GWP, R1234yf

R404A

HFC blend with a GWP of 3,922; widely used in (older) commercial and deep-freeze refrigeration, being phased out at an accelerated pace.

Because of its high GWP, an installation using R404A reaches the logbook threshold at as little as around 1.3 kg of charge. Replacement with lower-GWP alternatives is a recurring topic of conversation with customers.

See also: GWP, CO₂ equivalent, F-gas phase-down

R1234yf

HFO with a GWP of 4; used among other things in modern car air conditioning as a replacement for R134a.

See also: HFO, R134a

Recovery

Extracting and capturing refrigerant from an installation for reuse or destruction, instead of venting it.

See also: Refrigerant balance

Administration & work orders

The documents used to record work and refrigerant changes in an audit-proof way.

Operator / installation responsible party

The holder or owner of the installation who is legally responsible for leak checks and keeping the logbook.

The EU Regulation calls this the 'operator'. In practice the installation company handles the execution, but final responsibility lies with the operator.

See also: Logbook obligation, Leak check

Safety & inspections

LMRA, VCA and transport inspections that come up in refrigeration engineering.

VCA

Safety, Health and Environment Checklist Contractors: a certification for safe working that clients often require.

See also: LMRA

Knowing the terms is step one. Audit-proof record-keeping is step two.